The perforated inner shell has 3 32 diameter holes staggered at 3 16 on center for a clear open area of 23.
Double wall ductwork specification.
Double wall fittings are manufactured on our state of the art fabrication equipment.
Our double wall duct and fittings also control radiated noise better than similar sizes and shapes of externally insulated sheet metal duct.
Double wall duct and fittings can reduce radiated noise by 25 db or more compared with fiberglass duct board and by 30 db or more com pared with insulated flexible duct.
The outer shell of double wall construction for 2 or 3 inch insulation thicknesses finish 2 times the insulation thickness larger 4 inch and 6 inch respectively.
Construction class that is upstream of the vav boxes shall also meet seal class c.
Standard acoustical double wall is for noise control.
Langdon provides stainless steel and aluminum double wall duct and fittings for a wide range of environments including hospitals laboratories food and pharmaceutical plants.
In addition to the above any variable air volume system duct of 1 w g.
When a perforated inner liner is specified a retaining fabric must be wrapped between the perforated inner and the glass fiber insulation.
Double wall duct and fittings will consist of a perforated or solid inner liner 1 thick x 1 0 lb ft layer of glass fiber insulation and a solid outer pressure shell.
A comprehensive duct layout indicating sizes design airflows pressure class and routing of the duct system.
The types of fittings to be used based on the designer s calculations of fitting losses i e square versus 45 entry taps conical versus straight taps etc.
And up b all transverse joint and longitudinal seams 3 w g.
Ductwork will be spiral seam construction made from g 90 or better galvanized steel conforming to astm a653 a653m and a924 a924m standards lock forming quality lfq.
Duct wall penetrations 4 w g.
Langdon fabricates double wall ductwork with an inner perforated metal liner and fittings with an inner solid metal liner.
C transverse joints 2 w g.
Standard connections are slip fit with couplings.
Insulation will be flexible or semi rigid fiberglass with a maximum thermal conductivity of 0 27 btu hr ft 2 f inch.
This requirement is applicable to 20 gauge or less in thickness and 3 w g.
Double wall insulated spiral is available with solid or perforated liners.
Gasketed up to 36 flanged or spiralmate by ductmate industries connections are also available.
All double wall fittings are fabricated with stiffening beads on duct sizes 19 wide and larger which have more than 10 square feet of unbraced panel.
Mylar barrier is available as a barrier between perforated liner and insulation.